- DIN Controllers & Indicators - Product Manual
59305, Issue 7 – March 2014 P6100, P8100 & P4100 Model Group Page 59
ASCII Ident &
Message Types
Secondary
Proportional Band
Adjustable 0.0% to 999.9% of input
span. Read only when Self-Tuning.
Primary
Proportional Band
Adjustable 0.0% to 999.9% of input
span. Read only when Self-Tuning.
1 = Direct Acting, 0 = Reverse
Automatic Reset
Time
(or Loop Alarm
Time)
Integral Time Constant value.
(or Loop Alarm Time value in ON/OFF
control mode if Loop Alarm Enabled)
Read only if Self-Tuning.
ASCII range: 0 to 99m 59sec (99.59)
Modbus range: 0 to 5999
Derivative Time Constant value.
Read only if Self-Tuning.
ASCII range: 0 to 99m 59secs. (99.59)
Modbus range: 0 to 5999
0.5, 1, 2, 4, 8, 16, 32, 64,128, 256 or
512 seconds.
Lower limit of scaled input range
Upper limit of scaled input range
Alarm 1 active at this level
Alarm 2 active at this level
Bias value. 0% to 100% for single
control output or
-100% to +100% for dual outputs
20% to +20% of + ;
Negative value = Deadband
Positive value = Overlap
0.1% to 10.0% of input span
Used for Primary output on/off
differential and for combined Primary
and Secondary on/off differential.
0 = xxxx
1 = xxx.x
2 = xx.xx
3 = x.xxx
Read only if not Linear Input.
0.5, 1, 2, 4, 8, 16, 32, 64,128, 256 or
512 seconds.