Page 164 Specifications 59305, Issue 7 – March 2014
Output Specifications
Output Module Types
Option Slot 1 Module Options:
Relay, SSR drive, Triac or DC linear.
Limit Controllers have a fixed Latching Relay only.
Option Slot 2 Module Options:
Relay, Dual Relay, SSR drive, Triac or DC linear.
Dual Relay option on some models only.
Option Slot 3 Module Options:
Relay, Dual Relay, SSR drive, DC Linear or Transmitter
PSU. Dual Relay option on some models only.
Specifications of Output Types
Single pole double throw (SPDT).
2A resistive at 240V AC (120V when
directly driving motorised valves).
Limit Controller has a fixed 5A latching
relay, in Option Slot 1.
>500,000 operations at rated
voltage/current.
>100,000 operations at rated
voltage/current.
Basic Isolation from universal input
and SSR outputs.
2 x Single pole single throw (SPST)
with shared common.
2A resistive at 240V AC (120V when
directly driving motorised valves).
>200,000 operations at rated
voltage/current.
Reinforced safety isolation from inputs
and other outputs.
10V minimum at up to 20mA load.
Not isolated from universal input or
other SSR driver outputs.