- DIN Controllers & Indicators - Product Manual
Page 150 Glossary 59305, Issue 7 March 2014
Process Variable (PV) Type: General Definition
Process Variable is the variable to be measured by the primary input of the instrument. The
PV can be any parameter that can be converted into a electronic signal suitable for the input.
Common types are Thermocouple or PT100 temperature probes, or pressure, level, flow etc
from transducers which convert these parameters into linear DC signals (e.g. 4 to 20mA).
Linear signals can be scaled into engineering units using the Scale Range Lower Limit and
Scale Range Upper Limit parameters.
Also refer to Input Span, Offset, Scale Range Lower Limit and Scale Range Upper Limit.
Process Variable Offset Type: General Parameter
- Refer to Offset.
Rate (Derivative) Type: Controller Tuning Parameter
Rate is adjustable in the range 0 seconds (OFF) to 99 minutes 59 seconds. It defines how
the control action responds to the rate of change in the process variable. This parameter
should not be used in modulating value applications as it can cause premature wear due to
constant small adjustments to the valve position. The Rate parameter is not available if
primary control output is set to On-Off.
The Rate parameter is normally set to 0 seconds (OFF) on Valve Motor Drive controllers
because derivative action is not usually desirable in these applications.
Display code = , default value = 1.15.
Also refer to On-Off Control, PID, Process Variable, Tuning and Valve Motor Drive Control.
Remote Setpoint (RSP) Type: Controller Definition
Remote Setpoints use the Auxiliary Input option (a secondary analogue input) to adjust a
controller’s setpoint using an external linear DC Voltage or mA input signal, or in some cases
potentiometer or mV inputs. The Remote Setpoint value is constrained by the Setpoint Upper
Limit and Setpoint Lower Limit settings in the same way as a local setpoint. Typical
applications are Master/Slave and Cascade Control.
Display code = .
Also refer to Auxiliary Input, Cascade Control, Remote Input Range, Remote Setpoint Lower
Limit, Remote Setpoint Upper Limit, Setpoint and Setpoint Select.
Remote Auxiliary Input Range Type: Controller Parameter
Defines the type and range of the linear input signal (mADC, mVDC, VDC or potentiometer)
for the Auxiliary Input. mVDC and potentiometer are only available with the Full Auxiliary
input module. This input can be used for Remote Setpoint or Valve Position Indication
Display code = , default value =  for RSP inputs and  for Valve Position
Indication.
Also refer to Remote Setpoint, Setpoint and Valve Position Indication
Remote Setpoint Lower Limit Type: Controller Parameter
Defines the value of the Remote Setpoint when the RSP input signal is at its minimum value
(eg for a 4 to 20mA RSP, the value when 4mA is applied). It may be adjusted within the
range -1999 to 9999; (decimal position same as for process variable input). However, the
RSP value is always constrained within the Setpoint Upper Limit and Setpoint Lower Limits.
Display code = , default value = PV input range minimum.
Also refer to Remote Setpoint, Remote Setpoint Input, Remote Setpoint Upper Limit, Remote
Setpoint Offset, Setpoint and Setpoint Upper Limit and Setpoint Lower Limit.