- DIN Controllers & Indicators - Product Manual
Page 114 P6010 & P8010 Model Group 59305, Issue 7 – March 2014
Word Parameters
Table 30. P6010 & P8010 Communications - Word Parameters
ASCII Ident &
Message Types
If under-range = 62976 (<??>5 ASCII)
If over-range = 63232 (<??>0 ASCII)
Sensor break = 63488 (ASCII = n/a)
Maximum displayed value since this
was last reset. Shows under/over-
range or break values if appropriate.
Minimum displayed value since this
was last reset. Shows under/over-
range or break values if appropriate.
Accumulated alarm 1 active time since
this was last reset. Returns the over-
range value if the time exceeds 1000
minutes. Units = seconds in Modbus
Alarm 1 status.
0 = activated, 1 = safe
Alarm 2 status.
0 = activated, 1 = safe
Alarm 3 status.
0 = activated, 1 = safe
Change Indicator. 1 =
A parameter other than
instrument status or PV
has changed since the
last time the status
word was read.
Alarm 1 latched status.
0 = latched
1 = not latched or non-
latching output type
Modified PV = Actual PV + PV Offset.